5.1 Rack dimensions

One HP shall be 5.08 mm (RACK-001) and one rack unit shall be 44.45 mm (RACK-002), quoted from IEC 60297-3-101:2004. Both bind modules and enclosures.

A rack-mount frame, one that fastens into a 19-inch rack, shall meet IEC 60297-3-101:2004 and IEC 60297-3-100:2008 for the flange width, the flange mounting-hole positions and slot, the 3U height H1, and the 84 HP row width (RACK-003). A desktop or portable case needs no flanges; its rows keep the same HP, rack unit, and mounting-hole span (PANEL-009).

The figures RACK-003 applies:

Quantity Value Source
Panel width over mounting flanges 482.6 mm, ±0.4 mm IEC 60297-3-101:2004, Figure 3; IEC 60297-3-100:2008, Figure 2
Mounting-hole centers across flanges 465.1 mm IEC 60297-3-100:2008, clause 6.2 rack mounting grid
Mounting hole from outer edge 8.75 mm derived
Mounting-hole vertical steps 12.7 mm and 31.75 mm IEC 60297-3-100:2008, clause 6.2 rack mounting grid
3U flange mounting-hole span H2 57.15 mm IEC 60297-3-100:2008, Table 1
3U flange hole from each end H3 37.70 mm IEC 60297-3-100:2008, Table 1
Oval mounting slot 6.8 mm high, 14.7 mm deep IEC 60297-3-100:2008, detail A
3U front panel and subrack height H1 132.55 mm, ±0.4 mm IEC 60297-3-100:2008, Table 1
19-inch row width 84 HP IEC 60297-3-101:2004, Figure 3 (84 × 5.08 mm)
Three rack units 133.35 mm 3 × 44.45 mm
Mounting flange, each side narrower than 27.94 mm (482.6 − 84 × 5.08) / 2

EIS · IEC 60297-3-101 narrower than 27.94 mm, each side8.75 mm8.75 mmwider than 426.72 mm465.1 mm482.6 mm132.55 ± 0.4 mm1 HP, 5.08 mm84 HP37.70 mm57.15 mm37.70 mmoval mounting slot 6.8 mm high, 14.7 mm deep (detail A)

IEC 60297-3-100 applies H1, H2, and H3 to front panels, chassis, and subracks alike (its clause 5.1). Its detail A draws the slot as an oval open at the outer edge, 6.8 mm high (+0.5 / 0) and 14.7 mm deep (±1.2), and also permits a second hole type; the figure draws the open oval.

A front panel sits within H1, between the rails. The IEC publications do not set rail depth; 5.3 gives the recommended section.

The figures are in data/standards.json. The panel and flange figures (482.6 mm, H1, H2, H3, detail A, 1U, 84 × 5.08 mm) are read from the publications' own pages in the IEC's public preview: IEC 60297-3-100:2008 clause 5, Figure 2, and Table 1, and IEC 60297-3-101:2004 Figures 3 and 5 (bibliography). The rack mounting grid (465.1 mm centers, 12.7 mm and 31.75 mm steps) is in IEC 60297-3-100:2008 clause 6, beyond the preview, and is transcribed from the Schroff standards summary; where the two differ, the publication governs. The IEC publications are not stored in this repository.